hvac
AC Hose - High Side
for 2022 Rivian EDV 500 Dual Motor AWD (EDV) · AWD
Editorial review:Chris Hackleman — Master Technician · 20+ years · Jeff Moore — Master Lexus & Toyota Mechanic · 20+ years
Difficulty
Advanced
Time
4.0 h
Tools
12
Steps
14
✓Expert-verified. Personally reviewed and approved by OLP's master technicians (Chris Hackleman & Jeff Moore — 20+ years each). Always follow the vehicle's factory service information and torque specs.
This procedure covers the removal and replacement of the high-side AC hose on a 2022 Rivian EDV 500 electric delivery van, including refrigerant recovery and system recharge.
Warnings
⚠️R-1234yf refrigerant is mildly flammable. Ensure adequate ventilation and no ignition sources in work area. Never discharge refrigerant into atmosphere - EPA regulations require proper recovery.
⚠️Always disconnect the 12V battery and ensure high-voltage system is powered down before beginning work. Follow Rivian lockout/tagout procedures for high-voltage systems.
⚠Refrigerant can cause frostbite on contact with skin. Wear appropriate protective equipment including gloves and eye protection.
⚠AC system may retain pressure even when vehicle is off. Always verify system is depressurized before disconnecting lines.
ℹ️This procedure requires EPA Section 609 certification for mobile air conditioning work. Refrigerant handling must be performed by certified technicians.
Tools required
R-1234yf refrigerant recovery/recharge machineEssential
Refrigerant leak detectorEssential
Vacuum pumpEssential
AC manifold gauge set (R-1234yf compatible)Essential
Torque wrenchEssential
Socket set (metric)
Line wrench set (metric)Essential
Trim panel removal tools
Safety glasses for refrigerant workEssential
Refrigerant handling glovesEssential
New O-ring installation tool kit
UV dye and light (for leak checking)
Parts
- AC high-side hose assembly × 1 — Use OEM Rivian specification
- AC line O-ring kit × 1 — Use OEM Rivian specification
- AC system oil (POE oil for R-1234yf) × 1 — Use manufacturer-specified POE oil
- R-1234yf refrigerant × 1 — As required by system capacity
Preparation
- Park vehicle on level surface and engage parking brake
- Verify work area has adequate ventilation for refrigerant work
- Disconnect 12V battery negative terminal and wait 2 minutes
- Access the HV battery disconnect using Rivian service procedures and disable high-voltage system
- Allow AC system to equalize to ambient temperature if recently operated
- Identify the high-side AC hose routing from compressor to condenser
- Document refrigerant charge amount from underhood label for recharge reference
- Prepare R-1234yf recovery machine according to manufacturer instructions
Procedure
- 1Recover refrigerant from AC systemConnect the R-1234yf recovery machine to the AC service ports (high and low side). Start the recovery process and allow the machine to fully evacuate all refrigerant from the system. Recovery is complete when system pressure reads 0 PSI or in vacuum and no additional refrigerant is being extracted. Record the amount of refrigerant and oil recovered for recharge calculations.
- 2Access high-side hose connectionsRemove the front access panels or underbody shields as necessary to access the high-side AC hose. On the EDV 500, the high-side hose runs from the compressor (mounted near the front drive unit) to the condenser at the front of the vehicle. Remove any cable ties or retention clips securing the hose to the vehicle structure.
- 3Disconnect high-side hose at compressorUsing appropriate line wrenches to prevent damage, disconnect the high-side hose fitting at the compressor discharge port. Support the hose to prevent stress on connected components. Cap or plug the compressor port immediately to prevent moisture ingress and contamination. Inspect the O-rings and sealing surfaces for damage.
- 4Disconnect high-side hose at condenserLocate the condenser connection point at the front of the vehicle. Use line wrenches to carefully disconnect the high-side hose from the condenser inlet. Cap the condenser port immediately. Note the routing and any mounting bracket positions for reinstallation reference.
- 5Remove high-side hose assemblyRemove any remaining mounting brackets or clips securing the hose along its routing path. Carefully extract the high-side hose from the vehicle, noting the exact routing path, clearances from high-voltage components, and any grommets or isolators used. Take photos if necessary for installation reference.
- 6Inspect and prepare new hoseUnpack the new high-side hose assembly and verify it matches the original part. Install new O-rings at all connection points, lubricating them with clean POE oil compatible with R-1234yf systems. Ensure O-rings are properly seated in their grooves. Check that protective caps are in place on all fittings.
- 7Route and position new high-side hoseRoute the new high-side hose along the same path as the original, ensuring adequate clearance from high-voltage cables, drive unit components, and sharp edges. Install any grommets or isolators in their original positions. Verify the hose will not contact moving parts or heat sources.
- 8Connect high-side hose to condenserRemove the protective cap from the condenser port and new hose fitting. Inspect sealing surfaces for cleanliness. Hand-thread the connection to prevent cross-threading, then tighten using line wrenches. Follow manufacturer torque specifications if available, or tighten to industry-standard specification for AC line fittings of this size.
- 9Connect high-side hose to compressorRemove protective caps from the compressor discharge port and hose fitting. Verify O-ring is properly positioned and lubricated. Hand-thread the connection first, then tighten with line wrenches to proper specification. Ensure the hose alignment does not place stress on the compressor port.
- 10Secure hose and reinstall mounting hardwareInstall all mounting brackets and clips in their original positions to secure the high-side hose. Use new cable ties as needed to prevent hose movement or vibration. Verify all clearances are maintained and the hose cannot contact other components during vehicle operation.
- 11Evacuate AC systemConnect the vacuum pump to the AC service ports. Evacuate the system to a minimum of 29 inches Hg (500 microns or better is preferred). Maintain vacuum for at least 30-45 minutes to remove all moisture and air from the system. If vacuum does not hold, there may be a leak that requires repair.
- 12Leak test the systemAfter successful evacuation, introduce a small amount of R-1234yf refrigerant (approximately 50 PSI) into the system. Use a refrigerant leak detector to check all connections, particularly the newly installed high-side hose fittings at both ends. If leaks are detected, recover refrigerant, repair leaks, and repeat evacuation process.
- 13Recharge AC systemUsing the R-1234yf recharge machine, add the proper amount of refrigerant as specified on the vehicle underhood label. Add the appropriate amount of POE oil to compensate for oil lost during component replacement (typically 1-2 oz for hose replacement). Verify final system charge weight matches specification.
- 14Reinstall access panels and reconnect batteryReinstall any underbody shields, access panels, or trim pieces removed during the procedure. Reconnect the high-voltage system following Rivian reconnection procedures. Reconnect the 12V battery negative terminal.
Reassembly
- Ensure all AC line connections are tight and properly torqued
- Verify all protective shields and panels are reinstalled to prevent damage to AC lines
- Double-check that AC hose routing maintains clearance from high-voltage components and moving parts
- Confirm all cable ties and mounting brackets are secure
Verification
- Start the vehicle and allow it to complete its power-up sequence
- Turn on the AC system to maximum cooling and high fan speed
- Verify compressor engages (listen for operation or check system data)
- Check that both high and low side pressures are within normal operating range using manifold gauges
- Verify cold air is being produced at the cabin vents with temperature drop of at least 40°F from ambient
- Perform final leak check of all connections with refrigerant detector while system is running
- Verify no unusual noises or vibrations from the AC system during operation
- Test AC system operation through several on/off cycles to ensure proper function
- Check for any refrigerant odor in cabin or under hood that might indicate a leak